Application: | Power, Electronic, Instrument, Lighting, Rectifier, Audio |
---|---|
Phase: | Single |
Core: | Core-type Transformer |
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() ![]() |
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | EX200 |
Rated current In (A) (at 30 ℃) | 1,3,6,10,16,20,25,32,40,50,63 |
Polarity (width mm) | 1P(18), 1P+N, 2P (36), 3P (54) , 3P+N, 4P (72) |
Rated voltage Ue (V) | G65:AC230/400; G65H: AC230 /400; DC60 /1P,DC125 /2P |
Rated impulse withstand voltage Uimp (kV) | 4 |
Rated short-circuit capacity Icn | G65: 6kA;G65H:(AC400V: 10kA); (DC60V/1P: 20kA); (DC125V/2P: 20kA) |
Current limiting level | 3 |
B-type release characteristic | Protect loads with small short-circuit currents (such as power supplies, long cables, etc.), Instantaneous release range: 3~5ln |
C-type release characteristic | Protect conventional loads and distribution cables, Instantaneous release range: 5~10ln |
D-type tripping characteristic | Protect high starting current impact loads (such as motors, transformers, etc.), instantaneous trip range: 10~20ln |
Usage environment | Environmental temperature: -5 ℃ to+40 ℃; Moisture and heat resistance: Class 2 |
Attachments that can be installed | Auxiliary contact OF, alarm switch SD |
Mechanical lifespan (times) | twenty thousand |
Wiring capacity (mm2) | twenty-five |
Installation method | Standard guide rail |
Certificate | Obtain CCC certification certificate |
Compliant with standards | IEC 60898-1/GB 10963.1 |